VFD · FEEDBACK

Why a VFD Needs Fault, Ready and Running Feedback — Not Just a RUN Command

A PLC output saying RUN and a motor actually running are different facts. Feedback closes the state loop.

VFDFaultReadyRunningFeedback

A command is only the intention

The PLC output may be ON while the VFD is faulted, disabled or missing a permissive. For the same reason, an HMI running lamp should normally come from verified drive state rather than the command bit alone.

Closed-loop state
PLC RUN CMD→VFD→READY / RUN / FAULT→PLC decision

Think in at least three feedback states

FeedbackMeaningPLC use
ReadyDrive available to runRun permissive
RunningActual running stateStatus / next sequence step
FaultDrive abnormal conditionBlock run / alarm

Add a feedback timeout after the command

If Running does not arrive within a defined time after RUN is commanded, the PLC can identify a “commanded but not running” condition. This timeout is process logic, not a replacement for safety functions.

Treat fault reset as a separate action

Repeated automatic reset can hide the underlying cause. Separate the reset request and only allow it when the process and restart conditions are understood.